Arizona’s Trusted Partner for Gas Detection and Life Safety Systems.

Global Systems United
Home
Projects
Services
REQUEST A QUOTE
FAQ
Testimonials
Careers
Online Store
Resources
About
Our Products
Contact Us
Global Systems United
Home
Projects
Services
REQUEST A QUOTE
FAQ
Testimonials
Careers
Online Store
Resources
About
Our Products
Contact Us
More
  • Home
  • Projects
  • Services
  • REQUEST A QUOTE
  • FAQ
  • Testimonials
  • Careers
  • Online Store
  • Resources
  • About
  • Our Products
  • Contact Us
  • Sign In
  • Create Account

  • Orders
  • My Account
  • Signed in as:

  • filler@godaddy.com


  • Orders
  • My Account
  • Sign out


Signed in as:

filler@godaddy.com

  • Home
  • Projects
  • Services
  • REQUEST A QUOTE
  • FAQ
  • Testimonials
  • Careers
  • Online Store
  • Resources
  • About
  • Our Products
  • Contact Us

Account

  • Orders
  • My Account
  • Sign out

  • Sign In
  • Orders
  • My Account

Fire Alarm System vs. Sprinkler Monitoring System:

Fire Alarm System vs. Sprinkler Monitoring System:

 

When it comes to life safety systems, it's essential to understand the distinction between a sprinkler monitoring system and a fire alarm system. Although they both relate to fire protection, their functions, components, code requirements, and triggers for installation are very different.


What Is a Sprinkler Monitoring System?


A sprinkler monitoring system is designed specifically to supervise the operation of a building's fire sprinkler system. It does not detect fire or alert occupants directly. Instead, its purpose is to monitor whether the sprinkler system is ready and operational.


Key Functions:


  • Detects waterflow through the sprinkler pipes (indicating possible sprinkler activation)
     
  • Detects tampering with control valves (such as someone accidentally or intentionally closing a valve)
     
  • Sends a signal to a monitoring station if water is flowing or if a valve is tampered with
     

Typical Components:


  • Waterflow switch
     
  • Tamper switch
     
  • Pressure switch (optional)
     
  • Standalone communicator or dialer (often cellular)
     
  • One smoke detector above the panel or communicator (if required by AHJ)
     

Special Note:


Although sprinkler monitoring systems do not include general smoke detection, many jurisdictions still require a single smoke detector mounted above the sprinkler monitoring panel or communicator. This is to protect the monitoring equipment and ensure early warning if a fire originates near the control point. This requirement is usually enforced even though the system is not classified as a full fire alarm.


Code Reference:


  • Governed primarily by NFPA 13 and NFPA 72 for supervisory signal monitoring
     

Purpose:


  • Ensures the sprinkler system is always armed and ready
     
  • Sends alerts when valves are closed or if water flows unexpectedly
     
  • Does not include system-wide detection, occupant notification, or evacuation alerting
     

What Is a Fire Alarm System?


A fire alarm system is a complete life safety notification system that detects fire conditions and alerts both building occupants and emergency responders.


Key Functions:


  • Detects smoke, heat, or manual activation (via pull stations)
     
  • Activates visual and audible alarms (strobes and horns)
     
  • Sends automatic signals to the fire department or monitoring station
     
  • May initiate other safety features, such as elevator recall or door release
     

Typical Components:


  • Fire alarm control panel (FACP)
     
  • Smoke detectors
     
  • Heat detectors
     
  • Manual pull stations
     
  • Horns, strobes, or speaker systems
     
  • Fire department connection or dialer (phone line or cellular)
     
  • Duct smoke detectors (required to be monitored by the fire alarm panel)
     


Special Notes:


  • Most jurisdictions require a smoke detector above the fire alarm control panel (FACP) to protect the panel itself.
     
  • Duct smoke detectors, which detect smoke in HVAC systems, are required to be connected to and monitored by the fire alarm system. They must initiate a supervisory or alarm signal and cannot function as standalone devices.
     

Code Reference:


  • Governed by NFPA 72 (National Fire Alarm and Signaling Code)
     
  • Required based on occupancy group and maximum occupant load, as defined by the International Building Code (IBC) and local authority having jurisdiction (AHJ)
     

Purpose:


  • Provides early warning of fire conditions
     
  • Ensures occupants are alerted and able to evacuate
     
  • Automatically notifies emergency services
     


Why This Matters


Understanding the distinction is important for code compliance and safety. Some buildings may only require sprinkler monitoring due to their size and use. Othersβ€”based on occupant load, type of occupancy (e.g., restaurant, school, healthcare facility), or square footageβ€”are required to have a full fire alarm system.

Failing to install the correct system can result in failed inspections, delayed occupancy permits, or even legal liability in the event of an emergency.


Summary


  • A sprinkler monitoring system supervises the sprinkler system and reports valve tampering and waterflow events to a monitoring center
     
  • A fire alarm system detects fires and alerts people to evacuate, while also notifying emergency services
     
  • Fire alarm systems are required based on occupancy group and number of occupants, while sprinkler monitoring is required any time a sprinkler system is present, regardless of occupancy
     
  • Both systems may require a smoke detector above the panel, but only the fire alarm system provides full building coverage
     
  • Duct smoke detectors must be monitored by a fire alarm system and are not part of a sprinkler-only setup
     

🚨🚨 REQUEST A SERVICE 🚨🚨


Home | About | Projects | Services | Request a Quote | Contact Us  FAQ | Customer Page | Testimonials | Careers | Our Products | Online Store | Arizona CO2 Monitoring | Resources | Articles | Vendors | Privacy Policy | Terms & Conditions | Warranty Claims


Β© 2025 Global Systems United – All Rights Reserved.  

Life Safety Systems | ROC #297544 – CR67

This website uses cookies.

By continuing, you agree to our use of cookies to improve your browsing experience.

Got it